A heavy industrial press standing on a fabrication shop floor.

Guide 07 Defence fabrication and interconnection

What do continuity, insulation resistance and hipot tests check on a cable harness?

A cable harness is proved by four related but different tests. Continuity confirms every intended connection exists at low resistance. Shorts testing rules out unintended connections. Hipot testing applies high voltage to find weak insulation. Insulation resistance testing measures leakage current at a set DC voltage. IPC/WHMA-A-620 does not require shorts testing separately once hipot or insulation resistance has been run.

Topic
Defence fabrication and interconnection
Checked
23 September 2026
Sources
3
Questions
6

01

The standard behind harness acceptance: IPC/WHMA-A-620

IPC/WHMA-A-620 is the industry-consensus standard covering requirements and acceptance criteria for cable and wire harness assemblies, from crimped, mechanically secured and soldered terminations through to bundling, routing, labelling, shielding and final electrical testing. Revision E was published in 2022 and is the current edition.

The standard grades assemblies into three classes. Class 1 covers general products where basic function is the main requirement. Class 2 covers dedicated service products needing extended performance, where uninterrupted service is desirable but not critical. Class 3 covers high performance, harsh-environment products such as defence and aerospace work, where failure cannot be tolerated, and it carries the tightest acceptance criteria of the three.

  • Continuity: every intended connection exists at low resistance
  • Shorts (isolation): no unintended connection exists
  • Hipot (dielectric withstanding voltage): insulation withstands a high voltage without breakdown
  • Insulation resistance: leakage current stays within limit at a set DC voltage

02

Continuity and shorts, the baseline checks

Continuity testing confirms that every connection the drawing calls for actually exists, at a low resistance, wire by wire and pin by pin. It is the most basic check a harness tester runs and catches an open circuit, a missed crimp or a miswired connector before anything else is tested.

Shorts, or isolation, testing confirms the opposite: that no unintended connection exists between conductors that should be electrically separate. IPC/WHMA-A-620 does not require a separate shorts test once dielectric withstanding voltage or insulation resistance testing has been performed, since both of those tests would reveal an unintended short as well, but running it anyway catches a wiring error quickly and cheaply before the higher-voltage tests begin.

03

Hipot and insulation resistance, the two voltage tests

Dielectric withstanding voltage testing, commonly called hipot, applies a high voltage between conductors and to the shield to find weak or damaged insulation that would fail in service. IPC/WHMA-A-620's default hipot voltages are 1000 V DC for Class 2 assemblies, held for a 0.1 second dwell, and 1500 V DC for Class 3 assemblies, held for a 1 second dwell, where the drawing or customer specification does not set its own value.

Insulation resistance testing measures leakage current at a set, lower DC voltage rather than looking for a sudden breakdown, so it finds gradual degradation a hipot test can miss. The standard's minimum acceptance values differ by assembly length and type: 100 megohms or more for an assembly of three metres or less, 10 megohms or more for a longer assembly, and 500 megohms or more for coaxial cable. Wire and connector voltage ratings are checked first, since a hipot test run above a component's rating can damage good insulation rather than only reveal bad insulation.

04

What a harness tester actually does

An automated cable harness tester connects to every connector on the harness through purpose-built adapters and checks the wiring against a learned or programmed netlist, finding opens, shorts and miswires in seconds rather than the hours a manual continuity check would take. Higher-end testers add hipot and insulation resistance testing to the same cycle.

The value beyond speed is the record: results are logged against each harness's serial number, giving a traceable test history that a defence buyer's quality assurance representative can call for during inspection, rather than a signed test card with no underlying data behind it.

Asked next

Questions people also ask

What do continuity, insulation resistance and hipot tests check on a cable harness?

What is the difference between continuity and insulation resistance testing on a cable harness?

Continuity testing confirms that every intended connection exists at low resistance, catching an open circuit or a missed crimp. Insulation resistance testing measures leakage current at a set DC voltage between conductors that should be isolated, catching gradual insulation degradation rather than a broken connection. Both are run on the same harness because they check opposite failure modes: missing connection versus unwanted leakage.

What hipot test voltage does IPC/WHMA-A-620 set for a cable harness?

Where the customer drawing or specification does not set its own value, IPC/WHMA-A-620's default hipot, or dielectric withstanding voltage, test is 1000 V DC for a Class 2 assembly with a 0.1 second dwell, and 1500 V DC for a Class 3 assembly with a 1 second dwell. Wire and connector voltage ratings are checked first, since testing above a component's rating can damage sound insulation.

What is the minimum insulation resistance for a cable harness under IPC/WHMA-A-620?

The minimum acceptance value depends on the assembly: 100 megohms or more for an assembly of three metres or less, 10 megohms or more for a longer assembly, and 500 megohms or more for coaxial cable. These are the standard's default values where the customer drawing does not specify its own minimum for the particular harness.

Does a cable harness need a separate shorts test?

IPC/WHMA-A-620 does not require a separate shorts, or isolation, test once dielectric withstanding voltage or insulation resistance testing has been performed, since either of those tests would also reveal an unintended short between conductors. Many test houses run a quick shorts check anyway, before the higher-voltage tests, because it catches a basic wiring error faster and more cheaply.

What are the three classes in IPC/WHMA-A-620?

Class 1 covers general products where basic function is the main requirement. Class 2 covers dedicated service products needing extended performance where uninterrupted service is desirable but not critical. Class 3 covers high performance, harsh-environment products, including defence and aerospace work, where failure cannot be tolerated, and it carries the tightest acceptance criteria and the highest default hipot voltage of the three.

What does an automated cable harness tester check?

An automated harness tester connects to every connector through dedicated adapters and checks the wiring against a learned or programmed netlist, finding opens, shorts and miswires far faster than a manual check. Higher-end testers add hipot and insulation resistance testing to the same cycle and log every result against the harness's serial number, giving a traceable test record rather than a signed card with no data behind it.

Checked against

Sources

  1. 01A summary of the A-620 cable testing standard, Cirris Systems
  2. 02IPC/WHMA-A-620E:2022, Requirements and Acceptance for Cable and Wire Harness Assemblies, IPC and the Wiring Harness Manufacturer's Association, via ANSI Webstore
  3. 03Department of Defence Production, official website, Department of Defence Production, Ministry of Defence

This guide explains how the system works in general, as the documents above describe it, and was last checked on 23 September 2026. Rules and thresholds change: the governing document is the authority, not this page.

Have a requirement rather than a question?

Send the specification, the part or the drawing. The first reply says what we can do and what we need from you.